Commissioning of a fire suppression system

July 2017 Editor's Choice, Fire & Safety, Associations

Commissioning a newly installed fire suppression system is one of the most important functions. This is to prove the system functions correctly, the system is safe, the documentation set and certificates are complete, and the system is handed over to the client correctly.

The person responsible for commissioning a gaseous fire suppression system will have to go through several key points to ensure the system satisfies the requirements of the relevant standards and ensure the system will suppress a fire in the area it is protecting. The following are the standards to be referred to when commissioning a gaseous suppression system. Depending on the type of extinguishant used:

• SANS 246 – for electronic equipment installations.

• SANS 306 Part 4 – for CO2 systems.

• SANS 369 Part 1 – Electrical actuation of gaseous total flooding extinguishing systems.

• SANS 369 Part 2 – Mechanical actuation of gaseous total flooding and local application extinguishing systems.

• SANS 14520 – Gaseous fire-extinguishing systems – physical properties and system design.

There are two aspects to a gaseous fire suppression system, the electrical part and the mechanical part.

Electrical installation

The fire detection system must meet the basic requirements of SANS 10139, SANS 246 and SANS 369-1

The following points need to be considered:

1. Ensure the appropriate type of the detectors are installed and sufficient to cover the area they are protecting (1 per 50 m² minimum). Ensure the wind speed and flow direction of the air conditioning equipment has been taken into consideration as it influences the quantity of detectors to be used.

2. Ensure that the detectors are installed in coincidence connection, meaning two different detectors have to operate to activate the suppression system. The same applies for the ceiling void and floor void detectors.

3. The gas control unit is located at the entrance of the protected room with a manual switching device to enable mode of operation of the system to be changed from automatic to manual when personnel are entering the protected area.

4. There are visual and audible indications at the gas control unit to show the system status. This should also be provided at every entrance to the protected room. The operation of repeaters must function in conjunction with the main fire control panel to ensure that there is interlinking of the devices.

5. Audible and visual warnings are provided for, both inside the protected area and outside the area. The FDIA is promoting uniformity for audible and visual warnings for gas protected areas. Below is an operational philosophy we are asking all contractors to adhere to.

6. A manual release switch or break glass unit to release gas has been provided. The switch should be yellow in colour with operational instructions and signage indicating function and method of operation of the device.

7. If the area is normally occupied when the system is in automatic mode, then a hold switch should be provided to delay the countdown to discharge while the switch is held down. Upon release of the switch and provided the system is still in alarm state, the countdown should start from the beginning.

Electronic areas

8. Electronic areas have to comply with SANS246 and there are guidelines given on which type of detectors are to be used in these electronic equipment installations. The type of detectors will be determined by the category of risk identified. Three categories are mentioned in the standard and they are C – Medium Risk, D – High Risk and E – Critical Risk.

A high-sensitivity smoke detection / aspirating system is the only type of detection recommended for category D and E.

9. For high-risk category D and E rooms, it is a requirement that aspiration detection is installed at the return air grill to sense smoke picked up in the movement of air.

10. The type of detection, wind speed and wind flow direction of the air conditioning equipment influences the quantity of detectors to be used.

All of the above become the responsibility of the commissioning technician to ensure everything is installed as per the SANS requirements and functions correctly.

Mechanical installation

This section includes the cylinders and installation of gas distribution pipe and fittings. The mechanical check should involve the following:

1. Every gas system installation shall be provided with a gas hydraulic calculation which has to be checked by the commissioner.

2. The dimensions of the room should be measured to ensure they are the same as the hydraulic calculations provided.

3. The pipe size and layout is as per the hydraulic design.

4. The pipe fittings used shall be in accordance with the standards and be able to withstand system frictions and pressures.

5. The nozzle size and type is as per the design.

6. There is a dirt trap installed at the end of each pipe so that dust and foreign matter does not impede nozzle orifice.

7. The pipe work and cylinders are securely fixed so that there is no movement during discharge.

8. The gas cylinders are clearly labelled, showing the type of gas, capacity of cylinder, quantity of gas inside, date and approvals.

Room integrity test

9. All cable and other penetrations or openings into the room are adequately sealed to prevent extinguishant gas escaping out of the room.

10. A room integrity test should be carried out to confirm that the extinguishant gas will remain in the room for the required time (10 minutes for clean agent gasses) and a report for the room integrity test included in the documentation.

11. Some rooms will have openings during normal operations, like MCC rooms to allow to air circulation, in such cases dampers will have to be provided for. Aircon shut down units for server rooms need to be interfaced to the suppression system to switch off the aircon during discharge, if they are supplying fresh air to the room but recycling units can be left running and can actually assist in the dispersion and mixing of the extinguishing gas with in the risk area.

12. The type of agent used may necessitate the use of pressure vents, especially if it is an inert gas used as an extinguishant. This is to prevent damage to walls and windows due to increase in pressure within the room, caused by the gas discharge.

All of the above must be either witnessed by, or conducted by, the commissioner.

Documentation

The documentation for a suppression system should include the hydraulic calculations for pipe work, design concentration for the type of gas used, report on room integrity test, certificates and approvals for the system and equipment used. A signed certificate should then be given to the client that verifies the installed system operates correctly in accordance with requirements laid down by the designer and that the commissioner carries liability for the correct operation of the system.

Gas commissioners shall be registered at the SAQCC Fire and carry an identity card of such. We encourage end users to use FDIA registered companies as they have the relevant registrations, training and experience and are committed to working to the required standards.

For comments and enquiries please contact the FDIA on [email protected]



Credit(s)




Share this article:
Share via emailShare via LinkedInPrint this page



Further reading:

CCTV control room operator job description
Leaderware Editor's Choice Surveillance Training & Education
Control room operators are still critical components of security operations and will remain so for the foreseeable future, despite the advances of AI, which serves as a vital enhancement to the human operator.

Read more...
Amendments to the Private Security Industry Regulations
Technews Publishing Agriculture (Industry) News & Events Associations
SANSEA, SASA, National Security Forum, CEO, TAPSOSA, and LASA oppose recently published Amendments to the Private Security Industry Regulations regarding firearms.

Read more...
A passport to offline backups
SMART Security Solutions Technews Publishing Editor's Choice Infrastructure Smart Home Automation
SMART Security Solutions tested a 6 TB WD My Passport and found it is much more than simply another portable hard drive when considering the free security software the company includes with the device.

Read more...
Navigating the complexities of privileged access management
Editor's Choice Access Control & Identity Management
Privileged Access Management and Identity Access Management are critical pillars of modern cybersecurity, designed to secure access to sensitive resources, enforce principles like least privilege, and implement just-in-time access controls.

Read more...
Rewriting the rules of reputation
Technews Publishing Editor's Choice Security Services & Risk Management
Public Relations is more crucial than ever in the generative AI and LLMs age. AI-driven search engines no longer just scan social media or reviews, they prioritise authoritative, editorial content.

Read more...
Efficient, future-proof estate security and management
Technews Publishing ElementC Solutions Duxbury Networking Fang Fences & Guards Secutel Technologies OneSpace Technologies DeepAlert SMART Security Solutions Editor's Choice Information Security Security Services & Risk Management Residential Estate (Industry) AI & Data Analytics IoT & Automation
In February this year, SMART Security Solutions travelled to Cape Town to experience the unbelievable experience of a city where potholes are fixed, and traffic lights work; and to host the Cape Town SMART Estate Security Conference 2025.

Read more...
Enhancing safety in battery energy storage systems
Technoswitch Fire Detection & Suppression Products & Solutions Fire & Safety
The calibration-free Combustible Gas & VOC Sensor by Technoswitch can be configured to detect various flammable gases, including electrolyte vapours (VOC) and hydrogen, and is an indispensable tool for ensuring the safety of Li-ion battery storage systems.

Read more...
ESPRIT intelligent fire panel range
Technoswitch Fire Detection & Suppression Products & Solutions Fire & Safety
Technoswitch recently added the EN54-approved ESPRIT intelligent control panel range to its product portfolio to complement the existing TC5000 intelligent control panel range, aimed at small and medium sites that require a cost-effective, networkable fire alarm system.

Read more...
Historic Collaboration cuts ATM Bombings by 30%
Online Intelligence Editor's Choice News & Events Security Services & Risk Management
Project Big-Bang, a collaborative industry-wide task team, has successfully reduced ATM bombings in South Africa by 30,7% during the predetermined measurement period of November, December and January 2024/5.

Read more...
World-first safe K9 training for drug detection
Technews Publishing SMART Security Solutions Editor's Choice News & Events Security Services & Risk Management Government and Parastatal (Industry)
The Braveheart Bio-Dog Academy recently announced the results of its scientific research into training dogs to accurately detect drugs and explosives without harming either the dogs or their handlers.

Read more...