The need for integrity testing

August 2012 Fire & Safety

Many years ago when fixed extinguishing systems consisted only of Halon 1301 and CO2 and fixed system standards were in their infancy, full discharge testing was considered mandatory.

However, the 1996 edition of the NFPA 2001 standard went as far as to state, “a discharge test is generally not recommended”. In addition room integrity testing was introduced to replace discharge testing. Why is full-scale discharge testing now frowned upon around the world and why is room integrity testing a mandatory requirement of SABS and ISO codes?

Why discharge test?

Initially, discharge testing was performed to test the reliability of the electrical and mechanical fire extinguishing system and to validate the extinguishing concentrations. As the installation and equipment manufacturing standards became more stringent and the move towards the implementation of quality management systems became the norm rather than the exception it was found that the mechanical and electrical reliability of systems began improving. Statistical measurement techniques as required by ISO 9000 highlighted manufacturing problem areas sufficiently to implement timeous corrective actions.

One should also understand that comprehensive system testing prior to the issue of a full system approval at both extremes of the system design parameters validates the performance range of the equipment offered.

It should also be noted that a system discharge test may only verify the design for that particular system configuration at that particular point in time. The validation of performance criteria is established by the system approval certificate, which is issued by independent third parties (at arm’s length) after rigorous testing and if process manufacturing controls have been implemented by the manufacturers.

When performing a discharge test one only has seconds to establish where any problem may occur if the design concentration is not reached. Also, should the design concentrations not be reached then further expensive discharge testing will be required.

With the concerns over the depletion of the ozone layer, discharge testing of Halon systems was curtailed. This then spread to the chemical synthetic gasses due to their extraordinarily high global warming potential and consequential high environmental damage concerns. As a result, a new method of testing had to be found; that method of testing is enclosure integrity acceptance testing.

Understanding extinguishing concentration

All gas system design standards require a certain design concentration of extinguishant be achieved in a pre-defined time. What many people fail to grasp is that this concentration must be maintained for a minimum time period (generally 10 minutes for clean agents). To complicate matters two primary types of mixing occur during and after a gas discharge:

* Descending interface.

* Continuous mixing.

During the discharge, and providing the system has been correctly designed, there will be continuous mixing. After the discharge the mixing model will depend on the status of the air-conditioning system. These factors affect the extinguishing concentration profile.

What is room integrity testing?

Room integrity testing is a mandatory requirement of the gas extinguishing standard SABS/ISO 14520. In addition the standard states that the testing must be carried out every 12 months to validate the enclosure integrity. Failure to perform this annual testing, places the system performance responsibilities clearly on the shoulders of the end user.

Failure to perform the initial room integrity test is also a violation of the SABS design and installation code and places the system performance responsibilities on the shoulders of the contractor.

The test consists of pressurising the enclosure with calibrated fans that provide specific airflows at specific flow pressures. In addition, the exterior and interior pressures of the enclosure are monitored so as to determine the air leakage of the room.

The earlier NFPA 2001 standard only requires a single measurement to be performed, while the SABS/ISO standard requires multiple sets of test data to be recorded. The SABS/ISO requirement is therefore more accurate and can highlight equipment errors and prevents operator fudging of the results, since the minimum correlation factor and allowable standard deviation is specified.

The test result is provided as an equivalent leakage area (ELA) in square metres. This ELA is the sum total of leakage paths in the room.By utilising a computer model of the gas extinguishing agent properties and knowing the ELA, the gas extinguishing retention times for the minimum design concentration can be determined.

If the retention time is greater than 10 minutes then the room passes, if the retention time is less than 10 minutes then the room fails.

Why perform room integrity testing?

1. Room integrity testing is a mandatory requirement of the SABS/ISO clean agent standard. This applies to all gasses and all systems.

2. Although not mandatory it is highly recommended that room integrity be performed on CO2 installations.

3. Extinguishing concentration measurements in a discharge test generally overestimate the actual extinguishing concentration by a substantial margin.

4. Room integrity testing allows the total room leakage to be identified and if this leakage is too great remedial action can be taken immed­iately and the results of the remedial work checked.

5. One of the most important design aspects of all clean agent systems is correct room venting. This is also especially true of CO2 systems. High discharge rates (10 s) of the chemical synthetic gasses and high air displacement of the inerts (±40%) make venting a key issue.

6. Major savings to air conditioner running costs.





Share this article:
Share via emailShare via LinkedInPrint this page



Further reading:

New addressable fire control panels
Issue 3 2021, Johnson Controls Global Products , Fire & Safety
Johnson Controls launches FireClass FC600 addressable fire control panels in the UK and South Africa, featuring a new colour 4.3-inch LCD screen with 32 zonal LEDs to ensure intuitive operations for all users.

Read more...
All-in-one signalling device
Issue 2 2021, Bosch Building Technologies , Fire & Safety
The Avenar all-in-one 4000 offers a complete solution through the optional combination with all Avenar fire detectors as well as an innovative power concept that permits up to 125 devices per ring bus.

Read more...
Complete fire safety in any environment
Issue 2 2021, XtraVision , Fire & Safety
Fire safety on the African continent needs to consider the many applicable and different relevant standards, regulations and installation rules.

Read more...
Early fire detection for central distribution
Issue 2 2021, G2 Security , Fire & Safety
With a substantial value of goods housed in Spar’s large complex warehouse facility, early fire detection is essential and the best solution is aspirating smoke detection, also referred to as high sensitivity smoke detection.

Read more...
Early warning fire detection for clean rooms
Issue 2 2021 , Fire & Safety
Securiton SecuriSmoke ASD 53x series aspirating smoke detectors address all the key challenges and deliver early and reliable fire detection in clean rooms and associated controlled environments.

Read more...
Fire-safe security cabinets
Issue 2 2021, Gunnebo Africa , Fire & Safety
The Chubbsafes Fire File 31-inch is a four-drawer filing cabinet that offers a reliable and efficient storage solution with the added benefit of fire resistance for up to two hours.

Read more...
Fire safety for petrochemical environments in Ghana
Issue 2 2021, XtraVision , Fire & Safety
Hochiki Europe has supported the construction of a new petrochemical storage and distribution facility in Ghana, by supplying a range of innovative fire detection and alarm equipment.

Read more...
Wireless fire safety for office block
Issue 2 2021, G2 Security , Fire & Safety
It’s an old story: much planning has gone into the new office block and just as they are doing the final touches, someone points out there is no fire detection.

Read more...
Empty buildings pose a potential fire hazard
Issue 2 2021, Fidelity Services Group , Fire & Safety
With so many corporates having opted to work from home this past year, there is a much higher chance of maintenance and upkeep being neglected and a fire going undetected or starting unexpectedly.

Read more...
700 Series conventional fire detectors
Issue 1 2021, Johnson Controls Global Products , Fire & Safety, Products
New 700 Series fire detectors have built-in microprocessors that monitor and respond to smoke density, fixed temperature and rate-of-rise of temperature, while the drift compensation feature extends service life and reduces maintenance needs.

Read more...