Automatic fire detection systems

August 2007 Fire & Safety

Small fires too often result in large losses due to delays in detecting the fire and summoning help. This is particularly so when premises are unoccupied eg: at night, over weekends and public holidays.

Automatic fire detection systems are designed to give early warning of a fire condition. The response of a detector to fire is transformed into a visual and audible signal to alert building occupants to facilitate evacuation and initial attack on the fire. If the system is directly connected to a fire department control room, the brigade will be automatically summoned.

In addition, detection systems can be used to activate automatic smoke and fire doors, fire dampers and fire extinguishing systems or to shut-off airconditioning systems, pipelines, etc.

System components

Detectors

Detectors are designed to react to one or more of the following characteristics of fire:

* Heat.

* Smoke.

* Flames.

Detectors are either capable of being reset or not. The latter type require replacement after activation. Most re-settable types are also fitted with a small indicator light which goes on to indicate which detector was operated.

Heat detectors

There are two types. Fixed temperature detectors only activate when a predetermined temperature is reached, whereas rate of rise detectors response to abnormally rapid temperature increases. These also incorporate an upper fixed temperature limit. Heat detectors can be operated in the following ways.

i. Fusible alloys

The melting of an alloy at a predetermined temperature completes an electrical circuit to operate the alarm. Normal operating temperatures vary between 55°C and 180°C.

ii. Expansion of metals, gases or liquids

Metals - the expansion due to heat of metal rods, strips, coils or bows in a specific direction completes an electrical circuit and raises the alarm.

Gases - pneumatic detectors cause the expansion of air in a chamber to distend a flexible diaphragm, completing a circuit and raising the alarm.

Liquids - comprises a copper tube filled with a fluid and fitted with a metal bellows on each end. The movement of the bellows due to the expansion of the fluid in the tube completes the circuit.

iii. Electrical effect

Two main types are used. The line detector utilises the effect of heat on heat-sensitive electrical insulation which melts causing contact between two conductors to alarm.

The thermocouple type activates when a temperature difference between a shielded and unexposed thermocouple produces a voltage difference.

Smoke detectors

i. Ionisation type

These have a chamber or two chambers incorporating a radioactive source and a positive and negative electrode. Air within the chamber is irradiated and ionised creating positive or negative ions depending on whether electrons are gained or lost. These then move either to the positive or negative electrodes to become neutralised. This movement reduces the resistance of the air causing a small current to flow in the circuit.

When smoke particles enter the chamber charged ions attach themselves to the particles. The charged particles move more slowly enabling them to meet charged particles or ions of opposite polarity and become neutralised. A reduction in the current flowing in the chamber occurs initiating an alarm.

ii. Optical type

These detectors have a light source and photo-electric cell in a light proof housing which allows free ingress of smoke. They operate on the light scatter principle where light is deflected by the smoke particles which enter the chamber onto the photocell and/or the light obscuration principle where smoke entering the chamber obscures the light beamed onto the photocell. This change in light configuration is sensed, causing the detector to actuate.

Flame detectors

In addition to visible light, flames also emit infrared and ultra-violet radiation which is detectable. Infrared type - an infrared (IR) sensitive photocell, filter, amplifier, integrator and timer are used to detect IR radiation and will raise the alarm when the radiation detected is in the 4 Hz to 15 Hz frequency range. This range is characteristic of the flicker of a flame.

A scanning type which will rotate and monitor through 360° in the horizontal plane is also available. Radiation is reflected by the scanner onto an IR detecting photocell to trigger an alarm. Ultra-violet detectors use either an ultra-violet (UV) sensitive photocell or a UV sensitive gas-filled tube in conjunction with an amplifier to detect UV radiation from flames.

Other detectors

Linear smoke/heat detector (beam detector)

A light beam is focused directly or indirectly via a reflecting mirror onto a photocell. The turbulent effect caused when smoke or heat waves cross the beam is detected by the photocell and the alarm is raised.

Air sampling type

Sampling tubes connected to an ionisation chamber terminate with the enclosed protected area. Air from the compartment being monitored is passed through an ionisation chamber by sampling tubes and a motor driven fan. Combustion products are monitored and an alarm is raised if these reach a predetermined level.

Wiring

The wiring transmits signals from the detectors to the annunciator panel and to the audible alarms.

It should be protected from accidental damage and the installation thereof should be of the highest quality to facilitate signal transfer. The wiring should be in metal conduit and be kept away from lift and unprotected stair shafts and openings to reduce the possibility of damage by fire.

Note: When evacuation and voice communication systems are interconnected to the detection system all wiring should be of the fire resistant type.

Control/indicating equipment

The control unit acts as a terminal for the detector and internal and external alarm circuits. It houses the test facilities, alarm silence button, fire or fault signalling and power supply monitoring equipment.

The size of the control unit will depend on the complexity of the detection installation and the total number of zones of which it is comprised. Each zone has a series of detectors off a loop of wiring enabling easy location of a fire within a zoned compartment, usually restricted to about 2000 m² or less.

An indicator panel, together with a plan of the premises with zone identification should be provided at the main entrance of the building where it will be seen by fire brigade or other personnel responding to an alarm.

Alarms

Alarms, which should be of the highest quality, include sirens, hooters, bells and electronic audible devices.

A rough guide on minimum recommended sound intensities is:

General alarm

65 dBA or 5 dBA more than any background noise likely to last more than 30 seconds.

To wake people

75 dBA at the bed head with all doors closed.

Power supplies

Power should be available from two reliable sources, each capable of running the system independently.

Usually an AC main supply with a DC back-up supply of continuously charged batteries capable of functioning for 72 hours during a mains power failure.

Maintenance

Regular testing/checking should be carried out as follows:

Battery check - weekly.

Detector circuit check - daily (where applicable).

Fire Department connections

Unmonitored - daily.

Monitored - weekly.

References

Manual of Firemanship Book 9, HMSO.

Fire Safety Data Sheet, FPA UK.

Suppression and Detection Systems, Dr L. Bryan.

SABS Code of Practice 0139: 1981 - The Prevention, Automatic Detection and Extinguishing of Fire in Buildings.

Fire Protection Association of Southern Africa.





Share this article:
Share via emailShare via LinkedInPrint this page



Further reading:

From prevention to protection
Securex South Africa News & Events Fire & Safety
The Western Cape’s varied landscapes and rapid urban development present a range of fire safety challenges, from densely populated city centres to remote industrial sites, and from heritage buildings to new high-rise developments.

Read more...
Fire and gas safety
Fire & Safety Facilities & Building Management
Fire and gas safety is a critical component of every business’s risk management processes. While sometimes ignored until it is too late, safety solutions abound at Securex Cape Town 2025.

Read more...
Why Securex matters more than ever
Securex South Africa News & Events Fire & Safety Facilities & Building Management
Visitors will observe the application of integrated security solutions, including AI-enhanced surveillance, cloud-based access control, cybersecurity tools, and perimeter protection within residential, commercial, logistics, and industrial environments

Read more...
Fire Ops SA Partners with Matrix
News & Events Fire & Safety Residential Estate (Industry)
Fire Ops SA, a South African private fire and rescue service, has announced its partnership with Matrix Vehicle Tracking to launch FireStop, providing Matrix and Beame clients with direct access to a dedicated professional private fire service.

Read more...
Solar growth sparks fire safety concerns
Fire & Safety
With solar power now firmly established as a mainstream energy choice for South Africans, ASP Fire cautioned that poorly designed or badly installed systems are increasingly giving rise to dangerous fire incidents.

Read more...
Passive fire protection for lithium-ion batteries
Fire & Safety Residential Estate (Industry)
In response to the increasing threat of lithium-ion (Li-ion) battery fires, a passive fire protection solution called PyroBubbles is now available in South Africa and is distributed locally through PyroBrand.

Read more...
Fire safety in focus
Securex South Africa Fire & Safety News & Events
Firexpo Cape Town visitors will not only compare technologies side-by-side, but also connect with suppliers and experts who understand both the region’s regulatory framework and its unique environmental risks.

Read more...
Standards for fire detection
Fire & Safety Associations
Nick Collins discussed SANS 246 – Fire Protection for Electronic Equipment Installations – Code of Practice, as it pertains to electronic equipment installations, including construction, furniture and fittings, air conditioning, raised flooring and more.

Read more...
Why Securex matters more than ever
Securex South Africa News & Events Fire & Safety Facilities & Building Management
Visitors will observe the application of integrated security solutions, including AI-enhanced surveillance, cloud-based access control, cybersecurity tools, and perimeter protection within residential, commercial, logistics, and industrial environments

Read more...
Electrical fire safety in lithium-ion battery rooms
Fire & Safety Residential Estate (Industry) Products & Solutions
Pratliperl is a non-combustible, ultra-lightweight aggregate that can be mixed with cement and applied as a plaster or screed to walls, floors, and ceilings. When applied at just 30 mm thickness, it delivers a two-hour fire rating.

Read more...










While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd. | All Rights Reserved.