Standards for fire detection

SMART Fire & Safety 2025 Fire & Safety, Associations, Editor's Choice

In previous articles in the series on fire standards, we discussed the two main standards required for fire detection systems, namely, SANS 10400-T and SANS 10139. (See the last article at www.securitysa.com/24268r). We continue with fire detection standards by now looking at SANS 322 – Fire Detection and Alarm Systems for Hospitals.

While SANS 10139 remains the primary standard for fire detection systems, SANS 322 specifically addresses systems to be installed within hospitals or similar buildings. SANS 322 allows for some deviations from the SANS 10139 recommendations. Being a hospital, there are specific sensitive areas where certain detection equipment cannot be installed. We shall first take a look at sounders.

Sounders, according to SANS 10139, need to have a dB (Sound Pressure) operational rating of 65 dB or 5 dB above the ambient noise. In hospitals, this rating is only required in non-patient areas, such as service areas, typically including the foyer or main entrance of a hospital. This area normally has facilities such as a dispensary, gift shop, café, doctors’ rooms, etc. In patient areas, a dB rating of 45 dB to 55 dB or 5 dB above ambient noise is considered suitable.

Additionally, you would not want the surgeon conducting your brain surgery to suddenly have a sounder going off in the theatre. Therefore, visual alarms may be used in these areas. The same can be said for ICUs, critical care, etc. Additionally, visual alarms may be utilised at nurses’ stations. In wards or areas where patients can escape unaided, normal audible alarms may be utilised.

Manual call points also have some additional criteria compared to SANS 10139. In non-patient areas, manual call points must be installed as per SANS 10139, however, the additional criteria are as follows: In patient access areas, manual call points shall be installed at or close to each nurse’s station, at each exit or stairway (but not on stairway landings) and on both sides of main doorways between detection zones (in close proximity to the doors). SANS 322 further provides instructions for mental health facilities where manual call points may deviate from SANS 10139 if false alarms are likely to occur due to the deliberate operation of call points by patients. In these cases, manual call points need not be readily accessible to patients. However, they must be easily accessible to staff.

The category of system, as per SANS 10139, must be a Manual (M) and L1 category system. Detectors may only be omitted from areas based on a fire risk assessment. The detection system must be equipped with facilities for disabling fire detectors without isolating manual call points. Control and indicating equipment must be provided at the main entrance of the hospital as well as the entrance where the fire department will most likely enter.

Lift homing must, in the event of an alarm, return to the ground floor or the level of the final exit from the building and be disabled. The fire alarm system shall not control lifts specifically designed for emergency evacuation beds.

The fire alarm system must be monitored by a manned 24-hour remote monitoring station or fire brigade, and should follow the recommendations in SANS 10139.

Additional information pertaining directly to a hospital is available in SANS 322. However, it should be noted that SANS 322 must be used in conjunction with SANS 10139. All relevant handover procedures and documentation shall be followed as per SANS 10139.

SAQCC Fire can provide guidance on the requirements for fire detection systems in healthcare facilities, including hospitals. Please consult the website www.saqccfire.co.za for contact information.




Share this article:
Share via emailShare via LinkedInPrint this page



Further reading:

From prevention to protection
Securex South Africa News & Events Fire & Safety
The Western Cape’s varied landscapes and rapid urban development present a range of fire safety challenges, from densely populated city centres to remote industrial sites, and from heritage buildings to new high-rise developments.

Read more...
Fire and gas safety
Fire & Safety Facilities & Building Management
Fire and gas safety is a critical component of every business’s risk management processes. While sometimes ignored until it is too late, safety solutions abound at Securex Cape Town 2025.

Read more...
Why Securex matters more than ever
Securex South Africa News & Events Fire & Safety Facilities & Building Management
Visitors will observe the application of integrated security solutions, including AI-enhanced surveillance, cloud-based access control, cybersecurity tools, and perimeter protection within residential, commercial, logistics, and industrial environments

Read more...
Fire Ops SA Partners with Matrix
News & Events Fire & Safety Residential Estate (Industry)
Fire Ops SA, a South African private fire and rescue service, has announced its partnership with Matrix Vehicle Tracking to launch FireStop, providing Matrix and Beame clients with direct access to a dedicated professional private fire service.

Read more...
Solar growth sparks fire safety concerns
Fire & Safety
With solar power now firmly established as a mainstream energy choice for South Africans, ASP Fire cautioned that poorly designed or badly installed systems are increasingly giving rise to dangerous fire incidents.

Read more...
Passive fire protection for lithium-ion batteries
Fire & Safety Residential Estate (Industry)
In response to the increasing threat of lithium-ion (Li-ion) battery fires, a passive fire protection solution called PyroBubbles is now available in South Africa and is distributed locally through PyroBrand.

Read more...
Fire safety in focus
Securex South Africa Fire & Safety News & Events
Firexpo Cape Town visitors will not only compare technologies side-by-side, but also connect with suppliers and experts who understand both the region’s regulatory framework and its unique environmental risks.

Read more...
Standards for fire detection
Fire & Safety Associations
Nick Collins discussed SANS 246 – Fire Protection for Electronic Equipment Installations – Code of Practice, as it pertains to electronic equipment installations, including construction, furniture and fittings, air conditioning, raised flooring and more.

Read more...
Why Securex matters more than ever
Securex South Africa News & Events Fire & Safety Facilities & Building Management
Visitors will observe the application of integrated security solutions, including AI-enhanced surveillance, cloud-based access control, cybersecurity tools, and perimeter protection within residential, commercial, logistics, and industrial environments

Read more...
Electrical fire safety in lithium-ion battery rooms
Fire & Safety Residential Estate (Industry) Products & Solutions
Pratliperl is a non-combustible, ultra-lightweight aggregate that can be mixed with cement and applied as a plaster or screed to walls, floors, and ceilings. When applied at just 30 mm thickness, it delivers a two-hour fire rating.

Read more...










While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd. | All Rights Reserved.