Standards for fire detection

SMART Fire & Safety 2025 Fire & Safety, Associations, Editor's Choice

In previous articles in the series on fire standards, we discussed the two main standards required for fire detection systems, namely, SANS 10400-T and SANS 10139. (See the last article at www.securitysa.com/24268r). We continue with fire detection standards by now looking at SANS 322 – Fire Detection and Alarm Systems for Hospitals.

While SANS 10139 remains the primary standard for fire detection systems, SANS 322 specifically addresses systems to be installed within hospitals or similar buildings. SANS 322 allows for some deviations from the SANS 10139 recommendations. Being a hospital, there are specific sensitive areas where certain detection equipment cannot be installed. We shall first take a look at sounders.

Sounders, according to SANS 10139, need to have a dB (Sound Pressure) operational rating of 65 dB or 5 dB above the ambient noise. In hospitals, this rating is only required in non-patient areas, such as service areas, typically including the foyer or main entrance of a hospital. This area normally has facilities such as a dispensary, gift shop, café, doctors’ rooms, etc. In patient areas, a dB rating of 45 dB to 55 dB or 5 dB above ambient noise is considered suitable.

Additionally, you would not want the surgeon conducting your brain surgery to suddenly have a sounder going off in the theatre. Therefore, visual alarms may be used in these areas. The same can be said for ICUs, critical care, etc. Additionally, visual alarms may be utilised at nurses’ stations. In wards or areas where patients can escape unaided, normal audible alarms may be utilised.

Manual call points also have some additional criteria compared to SANS 10139. In non-patient areas, manual call points must be installed as per SANS 10139, however, the additional criteria are as follows: In patient access areas, manual call points shall be installed at or close to each nurse’s station, at each exit or stairway (but not on stairway landings) and on both sides of main doorways between detection zones (in close proximity to the doors). SANS 322 further provides instructions for mental health facilities where manual call points may deviate from SANS 10139 if false alarms are likely to occur due to the deliberate operation of call points by patients. In these cases, manual call points need not be readily accessible to patients. However, they must be easily accessible to staff.

The category of system, as per SANS 10139, must be a Manual (M) and L1 category system. Detectors may only be omitted from areas based on a fire risk assessment. The detection system must be equipped with facilities for disabling fire detectors without isolating manual call points. Control and indicating equipment must be provided at the main entrance of the hospital as well as the entrance where the fire department will most likely enter.

Lift homing must, in the event of an alarm, return to the ground floor or the level of the final exit from the building and be disabled. The fire alarm system shall not control lifts specifically designed for emergency evacuation beds.

The fire alarm system must be monitored by a manned 24-hour remote monitoring station or fire brigade, and should follow the recommendations in SANS 10139.

Additional information pertaining directly to a hospital is available in SANS 322. However, it should be noted that SANS 322 must be used in conjunction with SANS 10139. All relevant handover procedures and documentation shall be followed as per SANS 10139.

SAQCC Fire can provide guidance on the requirements for fire detection systems in healthcare facilities, including hospitals. Please consult the website www.saqccfire.co.za for contact information.




Share this article:
Share via emailShare via LinkedInPrint this page



Further reading:

Detect procurement fraud before losses escalate
Security Services & Risk Management News & Events Financial (Industry) Editor's Choice
Organisations need to move procurement fraud prevention closer to the point where suspicious activity occurs, rather than relying primarily on investigations after money has already been lost, according to SAS and FACTS Consulting.

Read more...
Hold the line
BlueVision Information Security Editor's Choice
While most businesses are still focused on guarding the wall, the perimeter today has moved to the login screen, according to Christo Coetzer, founder and managing director of BlueVision Technologies.

Read more...
Chemical gas extinguishing system
Red G Distributors Products & Solutions Fire & Safety
Red G Distributors manufactures its FK-5-1-12 chemical gas extinguishing system locally. This clean-agent fire suppression system protects high-value assets from fire and the effects of firefighting, allowing operations to resume quickly with no collateral damage.

Read more...
XERO aerosol range by Technoswitch
Technoswitch Fire Detection & Suppression Fire & Safety
XERO’s fire suppression technology delivers a compact, cost-effective, long-service-life fire-extinguishing solution. The range offers electrically activated units that can be integrated onto a fire detection and control systems, as well as standalone activated units.

Read more...
Fire safety in South Africa
Technoswitch Fire Detection & Suppression Technews Publishing SMART Security Solutions Fire & Safety Security Services & Risk Management Editor's Choice
Fire safety is sometimes ignored, sometimes relegated to whatever is cheapest, and sometimes treated with the seriousness it deserves, given that it focuses on protecting life and assets. SMART Security Solutions asked Brett Birch, MD of Technoswitch, for some insights into the realities of fire safety in South Africa.

Read more...
Nimbus remote fire alarm management
Technoswitch Fire Detection & Suppression Security Services & Risk Management Fire & Safety
Nimbus connects key stakeholders to their fire alarm systems, simplifying compliance with fire safety standards and greatly improving visibility into critical events, thereby augmenting first responder processes that save lives and protect assets.

Read more...
In-ear hearing protection for firefighters
Fire & Safety Products & Solutions
Savox has launched Savox Fire Protect, a fully integrated firefighter communication system combining active in-ear hearing protection and wireless push-to-talk in a single, purpose-designed solution.

Read more...
Video fire detection by Technoswitch
Technoswitch Fire Detection & Suppression Products & Solutions Fire & Safety
Video fire detection technology can complement broader fire detection strategies in environments where dust, dirt, fumes, moisture, light levels, temperature, or access conditions pose challenges for traditional technologies.

Read more...
Bigger warehouses, bigger fire risks
Fire & Safety
Steven Freudiger, Securiton’s South Africa-based marketing manager, explains how Early Warning Fire Detection with the new SecuriSmoke ASD 2000 can protect even the biggest modern warehouses.

Read more...
Directory of alarm & fire safety service providers
Perimeter Security, Alarms & Intruder Detection Fire & Safety
The Directory of Product and Solution Suppliers includes the details of companies that provide products, advice and services to the alarm, intrusion & perimeter sectors.

Read more...










While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd. | All Rights Reserved.