Standards for fire detection

SMART Fire & Safety 2025 Fire & Safety, Associations, Editor's Choice

In previous articles in the series on fire standards, we discussed the two main standards required for fire detection systems, namely, SANS 10400-T and SANS 10139. (See the last article at www.securitysa.com/24268r). We continue with fire detection standards by now looking at SANS 322 – Fire Detection and Alarm Systems for Hospitals.

While SANS 10139 remains the primary standard for fire detection systems, SANS 322 specifically addresses systems to be installed within hospitals or similar buildings. SANS 322 allows for some deviations from the SANS 10139 recommendations. Being a hospital, there are specific sensitive areas where certain detection equipment cannot be installed. We shall first take a look at sounders.

Sounders, according to SANS 10139, need to have a dB (Sound Pressure) operational rating of 65 dB or 5 dB above the ambient noise. In hospitals, this rating is only required in non-patient areas, such as service areas, typically including the foyer or main entrance of a hospital. This area normally has facilities such as a dispensary, gift shop, café, doctors’ rooms, etc. In patient areas, a dB rating of 45 dB to 55 dB or 5 dB above ambient noise is considered suitable.

Additionally, you would not want the surgeon conducting your brain surgery to suddenly have a sounder going off in the theatre. Therefore, visual alarms may be used in these areas. The same can be said for ICUs, critical care, etc. Additionally, visual alarms may be utilised at nurses’ stations. In wards or areas where patients can escape unaided, normal audible alarms may be utilised.

Manual call points also have some additional criteria compared to SANS 10139. In non-patient areas, manual call points must be installed as per SANS 10139, however, the additional criteria are as follows: In patient access areas, manual call points shall be installed at or close to each nurse’s station, at each exit or stairway (but not on stairway landings) and on both sides of main doorways between detection zones (in close proximity to the doors). SANS 322 further provides instructions for mental health facilities where manual call points may deviate from SANS 10139 if false alarms are likely to occur due to the deliberate operation of call points by patients. In these cases, manual call points need not be readily accessible to patients. However, they must be easily accessible to staff.

The category of system, as per SANS 10139, must be a Manual (M) and L1 category system. Detectors may only be omitted from areas based on a fire risk assessment. The detection system must be equipped with facilities for disabling fire detectors without isolating manual call points. Control and indicating equipment must be provided at the main entrance of the hospital as well as the entrance where the fire department will most likely enter.

Lift homing must, in the event of an alarm, return to the ground floor or the level of the final exit from the building and be disabled. The fire alarm system shall not control lifts specifically designed for emergency evacuation beds.

The fire alarm system must be monitored by a manned 24-hour remote monitoring station or fire brigade, and should follow the recommendations in SANS 10139.

Additional information pertaining directly to a hospital is available in SANS 322. However, it should be noted that SANS 322 must be used in conjunction with SANS 10139. All relevant handover procedures and documentation shall be followed as per SANS 10139.

SAQCC Fire can provide guidance on the requirements for fire detection systems in healthcare facilities, including hospitals. Please consult the website www.saqccfire.co.za for contact information.




Share this article:
Share via emailShare via LinkedInPrint this page



Further reading:

Detect fires in the early stages
Securiton Products & Solutions Fire & Safety
The SecuriSmoke range from Securiton offers various levels of coverage and power to suit every budget and application. What all the models have in common is that they can detect smoke in very small quantities.

Read more...
SecuriHeat ADW linear heat detector
Securiton Products & Solutions Fire & Safety
The SecuriHeat ADW linear heat detector uses sealed tubes positioned over the detection area, and a remotely positioned control unit detects pressure changes in the tubes brought about by changing temperature.

Read more...
Fire safety in commercial kitchens
Technews Publishing Kestrel Distribution Products & Solutions Fire & Safety Commercial (Industry)
Fire safety in commercial kitchens is becoming increasingly critical. Defender is Europe’s first EN 17446:2021-approved kitchen hood fire suppression system and offers the indispensable safety measures required.

Read more...
The crucial role of fire, smoke, and gas detectors
Fire & Safety Facilities & Building Management
From wireless detectors to integrated building management systems, the industry is seeing a significant shift towards more intelligent, more responsive solutions. ASP Fire CEO Michael van Niekerk shares insights into these innovations.

Read more...
South African fire standards in a nutshell
Fire & Safety Editor's Choice Training & Education
The importance of compliant fire detection systems and proper fire protection cannot be overstated, especially for businesses. Statistics reveal that 44% of businesses fail to reopen after a fire.

Read more...
Secutel maintains ISO certifications
News & Events Fire & Safety
Secutel Technologies has successfully recertified all four of its ISO standards, a reflection of its continued commitment to excellence, client trust, and operational integrity.

Read more...
Protecting solar panel installations
Technoswitch Fire Detection & Suppression Products & Solutions Fire & Safety
Vulcan Integrated Solutions partnered with Technoswitch and installed Protectowire’s Confirmed Temperature Initiation (CTI) Series Linear Heat Detection (LHD) system, specifically designed for harsh environments, to offer fire protection for solar panels.

Read more...
SABRIC appoints Andre Wentzel as interim CEO
News & Events Financial (Industry) Associations
The South African Banking Risk Information Centre (SABRIC) has announced the appointment of Andre Wentzel as interim chief executive officer, effective immediately.

Read more...
LidarVision for substation security
Fire & Safety Government and Parastatal (Industry) Editor's Choice
EG.D supplies electricity to 2,7 million people in the southern regions of the Czech Republic, on the borders of Austria and Germany. The company operates and maintains infrastructure, including power lines and high-voltage transformer substations.

Read more...
From the editor's desk: Regulations, standards and skills, but poor enforcement
Technews Publishing SMART Security Solutions Fire & Safety
South Africa depends on the carrot approach to fire safety; in other words, businesses choosing to do the right thing, as the stick (or enforcement of regulations) is unfortunately lacking.

Read more...










While every effort has been made to ensure the accuracy of the information contained herein, the publisher and its agents cannot be held responsible for any errors contained, or any loss incurred as a result. Articles published do not necessarily reflect the views of the publishers. The editor reserves the right to alter or cut copy. Articles submitted are deemed to have been cleared for publication. Advertisements and company contact details are published as provided by the advertiser. Technews Publishing (Pty) Ltd cannot be held responsible for the accuracy or veracity of supplied material.




© Technews Publishing (Pty) Ltd. | All Rights Reserved.